Danfoss T2 Thermostatic Expansion Valve

Sale price $25.00

Go kalles this summer with this vintage navy and white striped v-neck t-shirt from the Nike. Perfect for pairing with denim and white kicks for a stylish kalles vibe.

Model: 068Z3206 - R22/R407C
Add to Wishlist
Add to Compare

Availability: In stock
Danfoss T2 Thermostatic Expansion Valve

Danfoss T2 Thermostatic Expansion Valve

Danfoss T2 Thermostatic Expansion Valve Body

The Danfoss T2 is an internally equalized thermostatic expansion valve body designed to regulate liquid refrigerant injection into an evaporator according to the refrigerant superheat at the evaporator outlet.

The T2 series uses a separately selected interchangeable orifice assembly, allowing the valve capacity to be matched to the refrigerant, system capacity and operating conditions.

Available Models

Danfoss Code Refrigerant Equalization Temperature Range
068Z3206 R22 / R407C Internal -40°C to +10°C
068Z3400 R404A / R507A Internal -40°C to +10°C

Common Technical Specifications

Product type T2 thermostatic expansion valve body / element
Pressure equalization Internally equalized
Temperature range -40°C to +10°C / -40°F to +50°F
MOP charge No MOP
Inlet connection 3/8 inch flare
Outlet connection 1/2 inch flare
Valve body dimensions Approx. 79 × 26 × 65 mm / 3.11 × 1.02 × 2.56 in
Sensing bulb dimensions Ø14.5 × 50 mm / Ø0.57 × 1.97 in
Capillary tube length 1,500 mm / 1.5 m / 59 inches
Net weight 0.284 kg / 284 g / 0.626 lb
Gross weight 0.306 kg / 306 g / 0.675 lb
Product volume 0.489 L
Maximum working pressure 34 bar / 500 psig
Static superheat 4°C / 7.2°F
Superheat setting Adjustable
Body and connection material Brass
Flow direction Single flow
Valve configuration Angleway

Dimension note: Valve body dimensions exclude the coiled capillary tube and sensing bulb. The dimensions shown are product dimensions and should not be used as shipping package dimensions.

Interchangeable Orifice Selection

The cooling capacity is not determined by the valve body code alone. It depends on the interchangeable orifice installed in the valve.

Danfoss T2 orifice sizes include 0X, 00, 01, 02, 03, 04, 05 and 06. The correct orifice must be selected according to:

  • Refrigerant
  • Required cooling capacity
  • Evaporating temperature
  • Condensing temperature
  • Liquid temperature
  • Pressure drop across the valve

Package Information

The standard valve body includes the sensing bulb, 1.5 m capillary tube and bulb strap. The interchangeable orifice assembly and flare nuts are not included unless specifically stated in the product option or order confirmation.

Important Selection Notice

Please verify the complete Danfoss code, refrigerant, pressure equalization method, connection size and required orifice before ordering. Similar Danfoss product codes can have different refrigerants, MOP charges or temperature ranges and might not be interchangeable.