Frascold Z Series Semi-Hermetic Reciprocating Compressors
Go kalles this summer with this vintage navy and white striped v-neck t-shirt from the Nike. Perfect for pairing with denim and white kicks for a stylish kalles vibe.
Frascold Z Series Semi-Hermetic Reciprocating Compressors
Product Description
The Frascold Z Series is a range of six-cylinder semi-hermetic reciprocating compressors designed for commercial and industrial refrigeration applications.
The available models cover nominal motor ratings from 25 HP to 50 HP and volumetric displacements from 106.2 to 184.7 m³/h at 50 Hz. Multiple motor sizes are available for selected displacement versions, allowing the compressor to be matched more accurately to low-, medium- or high-temperature operating conditions.
The Z Series uses positive-displacement oil-pump lubrication and is suitable for capacity regulation, inverter operation and Frascold RSH capacity-control solutions. Final compressor selection must always be verified according to the refrigerant, evaporating temperature, condensing temperature, voltage and required cooling capacity.
Key Features
-
Six-cylinder semi-hermetic reciprocating design
-
Displacement range: 106.2–184.7 m³/h at 50 Hz
-
Nominal motor range: 18.6–37.3 kW
-
Positive-displacement oil-pump lubrication
-
Frascold POE68 lubricant
-
Maximum frequency: 70 Hz
-
Minimum frequency: 30 Hz
-
Part-winding-start motor configuration for standard 400 V executions
-
Optional stepped capacity regulation
-
Capacity-control range up to 100–83–67–50%
-
Compatible with Frascold RSH capacity-control heads
-
Suitable for inverter operation within the approved operating envelope
-
Compact semi-hermetic construction
-
Suction and discharge service valves
-
Oil level sight glass
-
Connections for crankcase heater, oil-pressure protection and discharge-temperature monitoring
Available Models and Electrical Data
Technical values below refer to typical 400 V, 3-phase, 50 Hz, PWS executions.
| Model | Motor | Displacement 50 Hz | Displacement 60 Hz | MRA | LRA | LRA DOL |
|---|---|---|---|---|---|---|
| Z25-106Y | 25 HP / 18.64 kW | 106.2 m³/h | 127.4 m³/h | 53.6 A | 118.3 A | 202.7 A |
| Z35-106Y | 35 HP / 26.10 kW | 106.2 m³/h | 127.4 m³/h | 60.2 A | 144.5 A | 239.2 A |
| Z30-126Y | 30 HP / 22.37 kW | 125.7 m³/h | 150.9 m³/h | 55.7 A | 132.6 A | 224.4 A |
| Z40-126Y | 40 HP / 29.83 kW | 125.7 m³/h | 150.9 m³/h | 71.9 A | 159.2 A | 273.0 A |
| Z40-154Y | 40 HP / 29.83 kW | 154.4 m³/h | 185.3 m³/h | 77.9 A | 159.2 A | 273.0 A |
| Z50-154Y | 50 HP / 37.29 kW | 154.4 m³/h | 185.3 m³/h | 90.4 A | 188.6 A | 321.4 A |
| Z40-168Y | 40 HP / 29.83 kW | 168.2 m³/h | 201.8 m³/h | 77.9 A | 159.2 A | 273.0 A |
| Z50-168Y | 50 HP / 37.29 kW | 168.2 m³/h | 201.8 m³/h | 90.4 A | 188.6 A | 321.4 A |
| Z50-185Y | 50 HP / 37.29 kW | 184.7 m³/h | 221.6 m³/h | 90.4 A | 188.6 A | 321.4 A |
Dimensions, Connections and Weight
Dimensions are shown as length × width × height.
| Model | Dimensions | Net Weight | Suction Valve | Discharge Valve | Oil Charge |
| Z25-106Y | 765 × 509 × 457 mm | 220 kg | 2-1/8 in / 54 mm | 1-3/8 in / 35 mm | 3.7 L |
| Z35-106Y | 806 × 509 × 457 mm | 223 kg | 2-1/8 in / 54 mm | 1-3/8 in / 35 mm | 3.7 L |
| Z30-126Y | 765 × 509 × 536 mm | 229 kg | 2-1/8 in / 54 mm | 1-3/8 in / 35 mm | 7.2 L |
| Z40-126Y | 806 × 509 × 536 mm | 240 kg | 2-5/8 in / 67 mm | 1-5/8 in / 42 mm | 7.2 L |
| Z40-154Y | 794 × 509 × 536 mm | 240 kg | 2-5/8 in / 67 mm | 1-5/8 in / 42 mm | 7.2 L |
| Z50-154Y | 794 × 509 × 536 mm | 244 kg | 2-5/8 in / 67 mm | 1-5/8 in / 42 mm | 7.2 L |
| Z40-168Y | 794 × 509 × 536 mm | 240 kg | 2-5/8 in / 67 mm | 1-5/8 in / 42 mm | 7.2 L |
| Z50-168Y | 794 × 509 × 536 mm | 244 kg | 2-5/8 in / 67 mm | 1-5/8 in / 42 mm | 7.2 L |
| Z50-185Y | 794 × 509 × 536 mm | 244 kg | 2-5/8 in / 67 mm | 1-5/8 in / 42 mm | 7.2 L |
General Technical Specifications
| Parameter | Specification |
| Compressor type | Semi-hermetic reciprocating compressor |
| Series | Frascold Z Series |
| Number of cylinders | 6 |
| Lubrication system | Positive-displacement oil pump |
| Lubricant | Frascold POE68 |
| Standard reference power supply | 400 V / 3 Ph / 50 Hz |
| Standard motor connection | Part-winding start, subject to order code |
| Minimum operating frequency | 30 Hz |
| Maximum operating frequency | 70 Hz |
| Maximum HP operating pressure | 30 bar |
| Maximum LP static pressure | 20.5 bar |
| Capacity regulation | Full load or optional stepped/inverter control |
| Available capacity steps | Up to 100–83–67–50% |
| Terminal-box protection | Configuration dependent; commonly IP65 |
| Refrigerant selection | Must be verified with Frascold Selection Software |
Refrigerant Compatibility
The Frascold Standard Series supports traditional refrigerants as well as selected low-GWP refrigerants and blends.
Commonly approved refrigerants for the listed Z Series configurations include:
-
R22
-
R134a
-
R404A
-
R407A
-
R407C on selected models
-
R407F
-
R448A
-
R449A
-
R450A
-
R452A
-
R507
-
R513A
Refrigerant approval and the permitted operating envelope depend on the exact compressor model, motor version, application and lubricant configuration. Always confirm the selection before ordering.
Typical Applications
-
Commercial refrigeration systems
-
Cold-storage rooms
-
Frozen-food storage
-
Supermarket refrigeration
-
Food-processing refrigeration
-
Ice-making equipment
-
Beverage cooling
-
Industrial refrigeration systems
-
Condensing units
-
Compressor racks
Capacity-Control Options
Depending on the selected configuration, the Z Series can be supplied or operated with:
-
Full-capacity operation
-
Frascold CC capacity-control heads
-
Frascold RSH capacity-control heads
-
Stepped capacity regulation up to 100–83–67–50%
-
Variable-frequency operation within the approved envelope
-
Unloaded-start heads where required
Capacity-control components are not automatically included unless stated in the quotation.
Standard and Optional Equipment
Typical equipment may include:
-
Suction and discharge shut-off valves
-
Oil level sight glass
-
Electronic motor-protection module
-
Discharge-temperature sensor
-
Electronic oil differential-pressure protection
-
Rubber vibration absorbers
-
Nitrogen holding charge
-
Crankcase heater connection
Optional equipment may include:
-
Crankcase heater
-
Capacity-control heads
-
RSH capacity-control system
-
Unloaded-start head
-
Electronic oil-level switch
-
Special motor voltage
-
Additional monitoring and protection accessories
Selection Notice
Cooling capacity cannot be determined from horsepower or displacement alone.
Before ordering, please provide:
-
Required refrigerant
-
Evaporating temperature
-
Condensing temperature
-
Required cooling capacity
-
Power supply and frequency
-
Application type
-
Required capacity-control method
We will verify the model and operating envelope using Frascold selection data.
| Model |