HONGSEN VAFX Series vibration eliminators are flexible piping components designed for installation in the suction and discharge lines of refrigeration and air-conditioning compressors.
The assembly combines a corrugated metal hose, braided wire sleeve, end connectors, clamping rings and copper tube connections. It helps absorb compressor-generated vibration, reduce vibration transmission through refrigerant piping and lower the risk of fatigue-related pipe damage.
The flexible structure can also accommodate limited thermal displacement, installation deviation and foundation settlement in refrigeration piping systems.
Key Features
- Designed for refrigeration and air-conditioning compressor piping
- Suitable for compressor suction and discharge lines
- SUS316L corrugated metal hose
- Braided wire sleeve for added mechanical protection
- ODF solder connections
- Helps reduce vibration and piping noise
- Compensates for limited thermal movement and installation deviation
- Corrosion-resistant and heat-resistant construction
- Compatible with applicable HCFC and HFC refrigerants
- Medium temperature range from −40°C to +150°C
Technical Specifications
| Item | Specification |
|---|---|
| Brand | HONGSEN |
| Series | VAFX |
| Product Type | Refrigeration Vibration Eliminator |
| Connection Type | ODF Solder |
| Corrugated Hose Material | SUS316L Stainless Steel |
| Applicable Refrigerants | HCFC and HFC refrigerants |
| Medium Temperature Range | −40°C to +150°C |
| Installation Position | Compressor suction or discharge piping |
| Function | Vibration absorption and piping displacement compensation |
Available Models
| Model | ODF Connection | Max. Working Pressure | Min. Static Bend Radius | Min. Dynamic Bend Radius |
|---|---|---|---|---|
| VAFX-038-10 | 3/8 in | 4.2 MPa | 80 mm | 180 mm |
| VAFX-012-12 | 1/2 in | 4.2 MPa | 95 mm | 215 mm |
| VAFX-058-16 | 5/8 in | 4.2 MPa | 120 mm | 270 mm |
| VAFX-034-19 | 3/4 in | 4.2 MPa | 145 mm | 325 mm |
| VAFX-078-22 | 7/8 in | 4.2 MPa | 160 mm | 360 mm |
| VAFX-100-25 | 1 in | 4.2 MPa | 175 mm | 400 mm |
| VAFX-118-28 | 1-1/8 in | 4.2 MPa | 175 mm | 400 mm |
| VAFX-114-32 | 1-1/4 in | 3.5 MPa | 225 mm | 510 mm |
| VAFX-138-35 | 1-3/8 in | 3.5 MPa | 225 mm | 510 mm |
| VAFX-158-42 | 1-5/8 in | 2.5 MPa | 280 mm | 640 mm |
Bend-radius values are minimum installation requirements. The vibration eliminator should not be twisted, excessively stretched or installed below the specified bend radius.
Applications
- Commercial refrigeration systems
- Cold room condensing units
- Compressor suction lines
- Compressor discharge lines
- Refrigerated warehouses
- Food-processing refrigeration systems
- Air-conditioning equipment
- Industrial refrigeration installations
Ordering Information
Please select the model according to:
- Refrigerant pipe outside diameter
- System design pressure
- Refrigerant type
- Suction or discharge-line application
- Required installation length and bend radius
Final compatibility should be confirmed using the complete compressor and refrigeration-system operating conditions.
| Model |
VAFX-038-10 — 3/8 in ODF, VAFX-012-12 — 1/2 in ODF, VAFX-058-16 — 5/8 in ODF, VAFX-034-19 — 3/4 in ODF, VAFX-078-22 — 7/8 in ODF, VAFX-100-25 — 1 in ODF, VAFX-118-28 — 1-1/8 in ODF, VAFX-114-32 — 1-1/4 in ODF, VAFX-138-35 — 1-3/8 in ODF, VAFX-158-42 — 1-5/8 in ODF |
|---|