KAIDELI KGVK V-Type Cabinet Air Cooled Condenser

Sale price $1,272.00

Go kalles this summer with this vintage navy and white striped v-neck t-shirt from the Nike. Perfect for pairing with denim and white kicks for a stylish kalles vibe.

Model: KGVK039-L2/A
Add to Wishlist
Add to Compare

KAIDELI KGVK V-Type Cabinet Air Cooled Condenser

KAIDELI KGVK V-Type Cabinet Air Cooled Condenser

Short Description

The KAIDELI KGVK Series features a V-type condenser coil arrangement, top-mounted axial fans and a lower equipment compartment for refrigeration system integration. Compare model-specific heat-rejection capacities, airflow and cabinet dimensions to select the right configuration for your project.

Product Description

The KAIDELI KGVK Series is a cabinet air cooled condenser designed for integration into refrigeration equipment assemblies. Its V-shaped coil arrangement and top-mounted axial fans provide upward air discharge, while the lower compartment offers space for equipment integration.

The published models in this selection provide reference heat-rejection capacities of 39.6–132.9 kW with R22 and 35.7–120.9 kW with R404A, based on an ambient temperature of 32°C and a condensing temperature of 45°C.

With two-, three- and four-fan configurations, the series offers a range of airflow rates and cabinet sizes for different refrigeration requirements. Select the appropriate model according to your refrigerant, compressor selection, operating temperatures and required condenser heat-rejection duty.

Key Features

  • V-Type Coil Arrangement: A V-shaped condenser layout within a cabinet enclosure for refrigeration equipment integration.
  • Top Air Discharge: Top-mounted axial fans direct discharge air upward.
  • Multiple Fan Configurations: Published models offer two-, three- and four-fan arrangements.
  • Fan Diameters from 550 to 630 mm: Different fan sizes and airflow rates support model-specific system matching.
  • Lower Equipment Compartment: Provides space for equipment integration, subject to the selected model’s factory drawing.
  • Detailed Selection Data: Compare heat rejection, internal volume, fan power, airflow, dimensions and connection sizes.

Applications

The KGVK Series can be considered for refrigeration systems requiring a cabinet-style air cooled condenser, including:

  • Cold rooms and refrigerated storage facilities
  • Food processing and storage systems
  • Commercial and industrial refrigeration installations
  • Custom refrigeration equipment assemblies

Final suitability depends on the complete system design and confirmed operating conditions.


Performance Specifications

Reference rating conditions: 32°C ambient air temperature / 45°C condensing temperature.

Capacity values represent condenser heat rejection, not evaporator cooling capacity or electrical consumption. Fan power is expressed as the number of motors × rated power per motor.

Model R22 Heat Rejection (kW) R404A Heat Rejection (kW) Internal Volume (L) Fan Power (W) Airflow (m³/h) Fan Diameter (mm)
KGVK039-L2/A 39.6 35.7 9.7 2 × 600 15,584 550
KGVK042-L2/A 42.5 38.4 11.3 2 × 600 15,988 550
KGVK047-L2/A 47.4 42.8 12.0 2 × 780 19,064 600
KGVK056-L2/A 56.8 50.8 13.2 2 × 800 22,830 630
KGVK059-L2/A 59.2 53.1 14.1 2 × 800 23,084 630
KGVK062-L2/A 62.7 56.9 16.2 2 × 800 23,536 630
KGVK074-L3/A 73.9 67.0 17.5 3 × 780 28,928 600
KGVK085-L3/A 85.7 76.6 18.9 3 × 800 34,020 630
KGVK093-L3/A 93.5 84.2 24.0 3 × 800 35,112 630
KGVK098-L3/A 97.9 88.8 26.9 3 × 800 35,388 630
KGVK102-L3/A 102.2 94.2 30.0 3 × 800 35,896 630
KGVK120-L4/A* Pending Pending Pending Pending Pending Pending
KGVK132-L4/A 132.9 120.9 36.4 4 × 800 47,716 630

KGVK120-L4/A: exact model designation, availability and technical specifications require factory confirmation.

Dimensions and Connections

Model L × W × H (mm) Mounting Dimensions (mm) Inlet Diameter (mm) Outlet Diameter (mm) Reference Weight (kg)
KGVK039-L2/A 1558 × 933 × TBC* 1278 × 834 32 25 235
KGVK042-L2/A 1558 × 1018 × 1555 1278 × 919 32 25 258
KGVK047-L2/A 1654 × 1018 × 1545 1374 × 919 32 25 268
KGVK056-L2/A 1744 × 1018 × 1545 1464 × 919 32 25 285
KGVK059-L2/A 1814 × 1058 × 1590 1534 × 959 32 25 295
KGVK062-L2/A 2224 × 1018 × 1545 1944 × 919 32 25 325
KGVK074-L3/A 2364 × 1018 × 1545 2084 × 919 32 28 358
KGVK085-L3/A 2564 × 1018 × 1545 2284 × 919 32 28 375
KGVK093-L3/A 2564 × 1143 × 1680 2284 × 1044 42 32 415
KGVK098-L3/A 2884 × 1143 × 1680 2604 × 1044 42 32 445
KGVK102-L3/A 2884 × 1227 × 1770 2604 × 1128 42 32 475
KGVK120-L4/A Pending Pending Pending Pending Pending
KGVK132-L4/A 3509 × 1227 × 1770 3229 × 1128 Confirm* 32 565

Mounting hole diameter is 13 mm for the published models. Mounting dimensions must be read with the applicable factory drawing. Weights are published equipment references, not packed shipping weights.

KGVK039-L2/A: the published height requires verification and is shown as TBC.

KGVK132-L4/A: published inlet diameters differ between sources, with values of 50 and 54 mm. Confirm the current factory connection.


How to Select Your Model

  1. Determine the required condenser heat-rejection duty and compressor selection.
  2. Specify the refrigerant, design ambient temperature and condensing temperature.
  3. Confirm voltage, phase, frequency and fan-control requirements.
  4. Check installation space, airflow clearances, pipe connections and service access.
  5. Review the current factory drawing, technical selection and scope of supply before ordering.
Model

KGVK039-L2/A, KGVK042-L2/A, KGVK047-L2/A, KGVK056-L2/A, KGVK059-L2/A, KGVK062-L2/A, KGVK074-L3/A, KGVK085-L3/A, KGVK093-L3/A, KGVK098-L3/A, KGVK102-L3/A, KGVK120-L4/A, KGVK132-L4/A

Recently viewed products