Danfoss T2 and TE2 Replaceable Orifice Assemblies - No. 01 to No. 06

Sale price $144.00

Go kalles this summer with this vintage navy and white striped v-neck t-shirt from the Nike. Perfect for pairing with denim and white kicks for a stylish kalles vibe.

Model: No. 01 - 068-2010
Add to Wishlist
Add to Compare

Availability: In stock
Danfoss T2 and TE2 Replaceable Orifice Assemblies - No. 01 to No. 06

Danfoss T2 and TE2 Replaceable Orifice Assemblies - No. 01 to No. 06

Product Description

Danfoss T2 and TE2 Orifice Assemblies

Danfoss replaceable orifice assemblies are designed for T2 and TE2 thermostatic expansion valves used in air-conditioning and commercial refrigeration systems.

Six orifice sizes are available. Each size provides a different refrigerant capacity, allowing the T2 or TE2 valve to be matched to the refrigerant, evaporator capacity and operating conditions of the system.

Key Features

  • Designed for Danfoss T2 and TE2 thermostatic expansion valves
  • Replaceable orifice assembly
  • Available in sizes No. 01 through No. 06
  • Official product type: ORF
  • SAE flare design
  • Suitable for multiple refrigerants
  • Temperature range: -40°C to +10°C
  • Net weight: approximately 0.013 kg per piece
  • Easy identification by orifice number and Danfoss code

Compatible Refrigerants

According to the official Danfoss specifications, these orifice assemblies are listed for:

  • R1234yf
  • R134a/R513A
  • R22/R407C
  • R23
  • R236fa
  • R404A/R507A
  • R407A
  • R407C
  • R448A
  • R449A
  • R452A
  • R454C
  • R455A

Important Selection Information

This listing is for the orifice assembly only. The thermostatic element and valve body are not included.

Cooling capacity varies according to the refrigerant and operating conditions. Always select the orifice by confirming:

  • Danfoss code number
  • Orifice number
  • Refrigerant
  • Required refrigeration capacity
  • Evaporating temperature
  • Condensing temperature
  • Liquid refrigerant temperature
  • Pressure drop across the valve

The thermostatic element must also be suitable for the refrigerant used in the system.

Rated Capacity Table

The following values are Danfoss Range N rated capacities.

Orifice Code R134a R22 R404A R407C
No. 01 068-2010 2.10 kW / 0.59 TR 3.50 kW / 1.00 TR 2.60 kW / 0.75 TR 3.50 kW / 1.00 TR
No. 02 068-2015 2.60 kW / 0.73 TR 4.70 kW / 1.30 TR 3.70 kW / 1.00 TR 4.80 kW / 1.40 TR
No. 03 068-2006 4.30 kW / 1.20 TR 8.00 kW / 2.30 TR 6.30 kW / 1.80 TR 8.10 kW / 2.30 TR
No. 04 068-2007 6.40 kW / 1.80 TR 12.10 kW / 3.40 TR 9.90 kW / 2.80 TR 12.40 kW / 3.50 TR
No. 05 068-2008 8.40 kW / 2.40 TR 16.70 kW / 4.80 TR 13.00 kW / 3.70 TR 16.50 kW / 4.70 TR
No. 06 068-2009 10.10 kW / 2.90 TR 19.70 kW / 5.60 TR 15.50 kW / 4.40 TR 19.70 kW / 5.60 TR


Danfoss Rating Conditions

  • Evaporating temperature: 4.4°C
  • Condensing temperature: 38°C
  • Liquid refrigerant temperature: 37°C

Actual capacity may differ under other operating conditions.

Technical Specifications

Specification Value
Product name Orifice for expansion valve
Product type ORF
Parts program T2/TE2
Used with Danfoss T2 and TE2
Design SAE flare only
Available sizes No. 01 to No. 06
Temperature range -40°C to +10°C
Net weight Approximately 0.013 kg
Gross weight Approximately 0.017-0.018 kg
Factory packing format Multipack
Factory packing quantity 25 pieces
Product line Air Conditioning and Commercial Refrigeration
PED category Article 4, Paragraph 3
Model

No. 01 - 068-2010, No. 02 - 068-2015, No. 03 - 068-2006, No. 04 - 068-2007, No. 05 - 068-2008, No. 06 - 068-2009

Recently viewed products