Danfoss TGEX / TGE Thermostatic Expansion Valves for R22 – Range N, Without MOP
먼저 견적을 확인한 후 결제하세요. 상품 가격에는 배송비가 포함되지 않습니다. 구매 요청 제출 시 결제할 필요가 없습니다.
주문 방법:
1) 장바구니에서 “주문 요청 작성하기”를 선택하고 상품 모델/사양, 수량과 전체 배송지 주소(국가 및 우편번호 포함)를 입력해 주세요.
2) 재고, 배송비를 포함한 총액과 예상 배송 기간을 확인해 드립니다.
3) 총액에 동의하시면 Shopify 결제 링크를 이메일로 보내 드립니다.
4) 해당 링크로 결제하시면 전액 입금 후 발송을 준비합니다.
구매 요청 제출만으로 주문이 완료되지는 않습니다. 배송 기간은 예상치입니다.
Danfoss TGEX / TGE Thermostatic Expansion Valves for R22 – Range N, Without MOP
Product Description
Danfoss TGEX / TGE thermostatic expansion valves use a sensing bulb and capillary tube to regulate liquid refrigerant flow to the evaporator. This R22 range combines a fixed orifice with external pressure equalization, balanced-port construction and adjustable superheat.
The Range N selection covers evaporating temperatures from −40°C to +10°C and is supplied without MOP. Twenty-one Danfoss codes are included, covering manufacturer nominal R22 capacities from 10 to 134 kW, with listed ratings from 3 to 38 TR.
Operating Range and Application
The −40°C figure is the lower limit of the published evaporating-temperature range. It is not a fixed operating point or a cold-room temperature setpoint.
Choose the valve according to the refrigerant, evaporator load, evaporating temperature, condensing conditions and pressure losses. Applications requiring a MOP charge should be checked against the appropriate charge and code.
Capacity and Model Identification
The nominal capacities are rated at an evaporating temperature of 4.4°C, condensing temperature of 38°C, liquid temperature ahead of the valve of 37°C and opening superheat of 4 K.
TGEX3, for example, corresponds to the listed 10 kW / 3 TR selection. The model suffix should not be interpreted as a kW value. TGE 10, TGE 20 and TGE 40 identify the manufacturer body families.
Connections and Control Features
The selected codes use inch-size ODF solder inlet and outlet connections, with a 1/4-inch ODF external equalization connection. Inlet and outlet sizes must be checked against the exact code.
TGE 10 and TGE 20 selections have 1.5 m capillary tubes, while TGE 40 selections have 3 m capillary tubes. Construction includes a brass body, copper connections and a stainless-steel power element, sensing bulb and capillary tube.
Published family data specifies a standard static superheat setting of 4 K, adjustable from 0 to 8 K, and an opening superheat of 4 K. Bi-flow duty should be selected using the manufacturer’s performance data for the intended direction.
Packing and Ordering
Supplier-listed carton quantities are 12 valves for TGE 10, 8 for TGE 20 and 6 for TGE 40.
For a quotation from XIAXUE Refrigeration, provide the complete Danfoss code, quantity, refrigerant, cooling duty, operating temperatures and tube sizes. For replacement enquiries, include the existing valve code and nameplate information.
| Model and Connection |
TGEX3 - 067N2150 - 3/8 x 5/8 in ODF, TGEX3 - 067N2151 - 1/2 x 5/8 in ODF, TGEX4 - 067N2152 - 1/2 x 7/8 in ODF, TGEX6 - 067N2153 - 1/2 x 5/8 in ODF, TGEX6 - 067N2154 - 1/2 x 7/8 in ODF, TGEX6 - 067N2155 - 5/8 x 7/8 in ODF, TGEX7.5 - 067N2156 - 5/8 x 7/8 in ODF, TGEX9 - 067N2460 - 5/8 x 7/8 in ODF, TGEX11 - 067N2157 - 5/8 x 7/8 in ODF, TGEX11 - 067N2158 - 5/8 x 1 1/8 in ODF, TGEX12 - 067N2159 - 5/8 x 7/8 in ODF, TGEX12 - 067N2160 - 5/8 x 1 1/8 in ODF, TGEX15 - 067N2161 - 5/8 x 1 1/8 in ODF, TGEX15 - 067N2162 - 7/8 x 1 1/8 in ODF, TGEX18 - 067N2163 - 7/8 x 1 1/8 in ODF, TGEX18 - 067N2164 - 7/8 x 1 3/8 in ODF, TGEX26 - 067N2165 - 7/8 x 1 3/8 in ODF, TGEX26 - 067N2166 - 1 1/8 x 1 3/8 in ODF, TGEX30 - 067N2167 - 7/8 x 1 3/8 in ODF, TGEX30 - 067N2168 - 1 1/8 x 1 3/8 in ODF, TGEX38 - 067N2169 - 1 1/8 x 1 3/8 in ODF |
|---|