Elitech LS-230 Three-Phase Split Cold Room Electrical Control System
Go kalles this summer with this vintage navy and white striped v-neck t-shirt from the Nike. Perfect for pairing with denim and white kicks for a stylish kalles vibe.
Elitech LS-230 Three-Phase Split Cold Room Electrical Control System
Product Description
The Elitech LS-230 is a three-phase split electrical control system designed for one-refrigeration-unit and one-cold-room applications.
The operating panel is separated from the electrical control box, allowing the control box to be installed close to the refrigeration unit while the operating panel is positioned in a convenient location. This arrangement helps separate operating controls from high-current components and can reduce the amount of power cable required.
The system manages the compressor, electric defrost heater and unit cooler while providing temperature control, motor protection, alarm inputs and optional remote communication.
Key Features
- Split operating panel and electrical control box
- Compressor, defrost and unit-cooler control
- Suitable for piston and scroll compressors
- Electric defrost
- Three temperature-sensor connections
- Dual room-temperature sensors
- Independent defrost-temperature sensor
- Compressor overload protection
- Phase-loss protection
- Phase-sequence protection
- Three-phase imbalance protection
- Inverse-time motor protection
- Cyclic or real-time-clock defrost
- External protection-signal inputs
- Optional Bluetooth, WiFi, 2G or 4G communication
- Remote monitoring capability
Technical Specifications
| Item | Specification |
|---|---|
| Power Supply | Three-phase 4-wire or 5-wire, 380 VAC ±10%, 50/60 Hz |
| Compressor Type | Piston or scroll compressor |
| Compressor Power | 5 HP, 10 HP or 15 HP |
| Compressor Contactor | 18 A, 25 A or 32 A according to model |
| Compressor Start Method | Direct start |
| Condenser Type | Air cooled |
| Cold Room Type | Fan-cooled cold room |
| Defrost Method | Electric defrost |
| Temperature Control Range | -40°C to 119°C |
| Control Accuracy | ±1°C |
| Display Resolution | 0.1°C |
| Sensor Type | NTC 10 kΩ at 25°C, B value 3435 K |
| Number of Sensors | Two room sensors and one defrost sensor |
| Compressor Restart Delay | 1–120 minutes, adjustable |
| Defrost Start Mode | Cyclic or clock defrost |
| External Protection Inputs | Two |
| Current Measurement Range | 0–80 A |
| Dimensions | 260 × 320 × 135 mm |
| Operating Temperature | -10°C to 60°C |
| Operating Humidity | 20% to 90%RH, non-condensing |
| Networking Options | Bluetooth, WiFi, 2G or 4G |