HONGSEN TH Series Replaceable Orifice Assemblies No. 1 to No. 6

Sale price $6.00

Go kalles this summer with this vintage navy and white striped v-neck t-shirt from the Nike. Perfect for pairing with denim and white kicks for a stylish kalles vibe.

Model: No. 1
Add to Wishlist
Add to Compare

HONGSEN TH Series Replaceable Orifice Assemblies No. 1 to No. 6

HONGSEN TH Series Replaceable Orifice Assemblies No. 1 to No. 6

Product Description

Product Overview

HONGSEN TH Series replaceable orifice assemblies are designed for use with compatible HONGSEN TH and THW thermostatic expansion valve bodies.

Six orifice sizes are available. Each size provides different nominal refrigeration capacities depending on whether the valve is used with R22, R134a or R404A.

The replaceable design allows the valve capacity to be adapted without replacing the complete thermostatic expansion valve body.

Key Features

  • Replaceable valve orifice assembly
  • Available in No. 1 to No. 6 sizes
  • Suitable for HONGSEN TH and THW valve bodies
  • Capacity selection for R22, R134a and R404A
  • Integrated filter component
  • Simplifies maintenance and capacity adjustment
  • Orifice selected according to refrigerant and operating capacity

Available Variants

Orifice Stock No. Model Code
No. 1 01.32.239 TH22-09-01
No. 2 01.32.240 TH22-09-02
No. 3 01.32.241 TH22-09-03
No. 4 01.32.242 TH22-09-04
No. 5 01.32.243 TH22-09-05
No. 6 01.32.244 TH22-09-06

Nominal Refrigeration Capacity

Orifice R22 TR R22 kW R134a TR R134a kW R404A TR R404A kW
No. 1 0.7 2.5 0.5 1.8 0.45 1.6
No. 2 1.0 3.5 0.8 2.6 0.6 2.1
No. 3 1.5 5.2 1.3 4.6 1.2 4.2
No. 4 2.3 8.0 1.9 6.7 1.7 6.0
No. 5 3.0 10.5 2.5 8.6 2.2 7.7
No. 6 4.5 15.5 3.0 10.5 2.6 9.1

Compatibility

Designed for the following HONGSEN valve bodies:

  • TH22 and TH22W
  • TH134 and TH134W
  • TH404 and TH404W

The model codes use the TH22-09 prefix, but the numbered orifices are selected across the TH family according to refrigerant and required capacity.

Important Selection Notice

Nominal capacities are reference values under the manufacturer’s stated rating conditions. The final orifice must be selected according to refrigerant, evaporating temperature, condensing temperature, superheat, subcooling and required system capacity.

Model