HONGSEN ERF22 and ERF22W R22 Thermostatic Expansion Valves
Go kalles this summer with this vintage navy and white striped v-neck t-shirt from the Nike. Perfect for pairing with denim and white kicks for a stylish kalles vibe.
HONGSEN ERF22 and ERF22W R22 Thermostatic Expansion Valves
Product Description
The HONGSEN ERF22 and ERF22W Series thermostatic expansion valves are designed to regulate the flow of R22 refrigerant into direct-expansion evaporators according to the evaporator outlet superheat.
Two connection and pressure-equalization configurations are available:
- ERF22: internally equalized valve with metric flare connections
- ERF22W: externally equalized valve with inch SAE flare connections and a 1/4 SAE external equalizer port
Multiple orifice sizes are available to cover nominal refrigeration capacities from 3.5 to 52.7 kW under the manufacturer’s stated rating conditions. Selecting the correct model requires confirmation of the refrigerant, cooling capacity, evaporating temperature, condensing temperature, pressure drop and required connection sizes.
The complete valve model and connection configuration should be confirmed before ordering.
Key Features
- Designed for R22 refrigeration systems
- Automatic refrigerant-flow regulation according to superheat
- Internal and external equalization options
- Metric flare and inch SAE flare configurations
- Multiple orifice sizes from Ø1.0 to Ø9.0
- Nominal capacities from 3.5 to 52.7 kW
- Integrated inlet filtering component
- Adjustable valve mechanism
- Suitable for commercial refrigeration and cold-storage systems
- Multiple connection sizes for different system capacities
Technical Specifications
| Parameter | Specification |
|---|---|
| Brand | HONGSEN |
| Product Family | ERF Series |
| Product Type | Thermostatic Expansion Valve |
| Refrigerant | R22 |
| ERF22 Configuration | Internal equalization |
| ERF22 Connection Type | Metric flare |
| ERF22W Configuration | External equalization |
| ERF22W Connection Type | Inch SAE flare |
| External Equalizer | 1/4 SAE on ERF22W |
| Available Orifice Sizes | Ø1.0–Ø9.0 |
| Nominal Capacity Range | 3.5–52.7 kW |
| Capacity Range | 1.0–15.0 TR |
| Standard Rating Evaporating Temperature | +5°C |
| Standard Rating Condensing Temperature | +40°C |
| Standard Rating Subcooling | 2°C |
| Main Application | Refrigerant flow control for direct-expansion evaporators |
Available Models
ERF22 Metric-Flare Models
| Model | Stock Connection Reference | Nominal Capacity | Inventory SKU |
|---|---|---|---|
| ERF22-Ø1.0 | Dg8 × Dg10, metric | 1.0 TR / 3.5 kW | 5250-000A-Ø1.0 |
| ERF22-Ø1.5 | Dg8 × Dg10, metric | 1.6 TR / 5.6 kW | 5250-000A-Ø1.5 |
| ERF22-Ø2.0 | Dg8 × Dg10, metric | 2.0 TR / 7.0 kW | 5250-000A-Ø2.0 |
| ERF22-Ø3.0 | Dg8 × Dg10, metric | 3.0 TR / 10.5 kW | 5250-000B |
| ERF22-Ø4.0 | Dg8 × Dg10, metric | 5.0 TR / 17.6 kW | 5250-000C |
| ERF22-Ø5.0 | Dg8 × Dg13, metric | 6.0 TR / 21.0 kW | 5252-000A |
| ERF22-Ø6.0 | Dg8 × Dg13, metric | 7.5 TR / 26.0 kW | 5252-000B |
| ERF22-Ø7.0 | Dg10 × Dg13, metric | 8.5 TR / 29.9 kW | ERF22-7-00G |
| ERF22-Ø8.0 | Dg10 × Dg13, metric | 12.0 TR / 42.2 kW | ERF22-8-00G |
| ERF22-Ø9.0 | Dg10 × Dg13, metric | 15.0 TR / 52.7 kW | ERF22-9-00G |
ERF22W Inch-Flare Models
| Model | Inlet × Outlet | External Equalizer | Nominal Capacity | Inventory SKU |
|---|---|---|---|---|
| ERF22W-Ø3.0 | 3/8 × 1/2 SAE | 1/4 SAE | 3.0 TR / 10.5 kW | 5261-000B |
| ERF22W-Ø4.0 | 3/8 × 1/2 SAE | 1/4 SAE | 5.0 TR / 17.6 kW | 5261-000C |
| ERF22W-Ø5.0 | 1/2 × 5/8 SAE | 1/4 SAE | 6.0 TR / 21.0 kW | 5263-000A |
| ERF22W-Ø6.0 | 1/2 × 5/8 SAE | 1/4 SAE | 7.5 TR / 26.5 kW | 5263-000B |
| ERF22W-Ø7.0 | 1/2 × 5/8 SAE | 1/4 SAE | 8.5 TR / 29.9 kW | ERF22W-7-00Y |
| ERF22W-Ø9.0 | 1/2 × 5/8 SAE | 1/4 SAE | 15.0 TR / 52.7 kW | ERF22W-9-00Y |
Model Selection Guidance
Select the required valve according to:
- Refrigerant type
- Required nominal cooling capacity
- Evaporating and condensing temperatures
- Liquid-line pressure drop
- Internal or external equalization requirement
- Inlet and outlet connection sizes
- Evaporator pressure drop
- Required orifice size
External equalization is recommended where the evaporator or distributor creates a significant pressure drop. Final selection should be completed by a qualified refrigeration technician.
Applications
- Walk-in cooler and freezer systems
- Commercial refrigeration equipment
- Cold-storage condensing units
- Display cabinets
- Refrigerated warehouses
- Food-processing refrigeration systems
- Direct-expansion evaporators
- Other compatible R22 refrigeration systems
Installation Notes
- Confirm the refrigerant and valve capacity before installation.
- Check the flow-direction arrow on the valve body.
- Install the sensing bulb securely on a clean horizontal suction line.
- Position the bulb according to accepted refrigeration practice.
- Connect the external equalizer downstream of the sensing-bulb position.
- Prevent excessive installation heat from reaching the power element.
- Leak-test the system after installation.
- Installation and adjustment must be performed by a qualified refrigeration technician.
| Series |
ERF22, ERF22W |
|---|---|
| Model |
ERF22-Ø1.0, ERF22-Ø1.5, ERF22-Ø2.0, ERF22-Ø3.0, ERF22-Ø4.0, ERF22-Ø5.0, ERF22-Ø6.0, ERF22-Ø7.0, ERF22-Ø8.0, ERF22-Ø9.0, ERF22W-Ø3.0, ERF22W-Ø4.0, ERF22W-Ø5.0, ERF22W-Ø6.0, ERF22W-Ø7.0, ERF22W-Ø9.0 |