HONGSEN VAFX Series Refrigeration Vibration Eliminators

Sale price $8.00

Go kalles this summer with this vintage navy and white striped v-neck t-shirt from the Nike. Perfect for pairing with denim and white kicks for a stylish kalles vibe.

Model: VAFX-038-10 — 3/8 in ODF
Add to Wishlist
Add to Compare

Availability: In stock
Categories: Pipes & Fittings
HONGSEN VAFX Series Refrigeration Vibration Eliminators

HONGSEN VAFX Series Refrigeration Vibration Eliminators

Description

Product Overview

HONGSEN VAFX Series vibration eliminators are flexible piping components designed for installation in the suction and discharge lines of refrigeration and air-conditioning compressors.

The assembly combines a corrugated metal hose, braided wire sleeve, end connectors, clamping rings and copper tube connections. It helps absorb compressor-generated vibration, reduce vibration transmission through refrigerant piping and lower the risk of fatigue-related pipe damage.

The flexible structure can also accommodate limited thermal displacement, installation deviation and foundation settlement in refrigeration piping systems.

Key Features

  • Designed for refrigeration and air-conditioning compressor piping
  • Suitable for compressor suction and discharge lines
  • SUS316L corrugated metal hose
  • Braided wire sleeve for added mechanical protection
  • ODF solder connections
  • Helps reduce vibration and piping noise
  • Compensates for limited thermal movement and installation deviation
  • Corrosion-resistant and heat-resistant construction
  • Compatible with applicable HCFC and HFC refrigerants
  • Medium temperature range from −40°C to +150°C

Technical Specifications

Item Specification
Brand HONGSEN
Series VAFX
Product Type Refrigeration Vibration Eliminator
Connection Type ODF Solder
Corrugated Hose Material SUS316L Stainless Steel
Applicable Refrigerants HCFC and HFC refrigerants
Medium Temperature Range −40°C to +150°C
Installation Position Compressor suction or discharge piping
Function Vibration absorption and piping displacement compensation

Available Models

Model ODF Connection Max. Working Pressure Min. Static Bend Radius Min. Dynamic Bend Radius
VAFX-038-10 3/8 in 4.2 MPa 80 mm 180 mm
VAFX-012-12 1/2 in 4.2 MPa 95 mm 215 mm
VAFX-058-16 5/8 in 4.2 MPa 120 mm 270 mm
VAFX-034-19 3/4 in 4.2 MPa 145 mm 325 mm
VAFX-078-22 7/8 in 4.2 MPa 160 mm 360 mm
VAFX-100-25 1 in 4.2 MPa 175 mm 400 mm
VAFX-118-28 1-1/8 in 4.2 MPa 175 mm 400 mm
VAFX-114-32 1-1/4 in 3.5 MPa 225 mm 510 mm
VAFX-138-35 1-3/8 in 3.5 MPa 225 mm 510 mm
VAFX-158-42 1-5/8 in 2.5 MPa 280 mm 640 mm

Bend-radius values are minimum installation requirements. The vibration eliminator should not be twisted, excessively stretched or installed below the specified bend radius.

Applications

  • Commercial refrigeration systems
  • Cold room condensing units
  • Compressor suction lines
  • Compressor discharge lines
  • Refrigerated warehouses
  • Food-processing refrigeration systems
  • Air-conditioning equipment
  • Industrial refrigeration installations

Ordering Information

Please select the model according to:

  • Refrigerant pipe outside diameter
  • System design pressure
  • Refrigerant type
  • Suction or discharge-line application
  • Required installation length and bend radius

Final compatibility should be confirmed using the complete compressor and refrigeration-system operating conditions.