Danfoss T2 / TE2 Orifice Assemblies with Filter – Flare Version
お見積もりを確認してからお支払いください。 商品価格に送料は含まれません。リクエストの送信時にお支払いは不要です。
ご注文の流れ:
1)カートで「注文リクエストの入力へ進む」を選び、商品型番・仕様、数量、お届け先の住所(国・郵便番号を含む)をご入力ください。
2)当店が在庫、送料込みの合計金額、配送予定をご案内します。
3)合計金額にご同意いただいた後、Shopifyのお支払いリンクをメールでお送りします。
4)リンクからお支払いいただき、全額入金後に発送を手配します。
リクエストの送信だけでは注文は完了しません。配送日数は目安です。
Danfoss T2 / TE2 Orifice Assemblies with Filter – Flare Version
Product Description
Danfoss T2 / TE2 Orifice Assemblies with Filter are replaceable capacity-setting components for compatible thermostatic expansion valves. This range includes eight orifice sizes, from No. 0X to No. 06, for the flare-connection assembly version.
Each variant combines the orifice size with its Danfoss code number, helping customers specify replacement components accurately. The thermostatic valve element/body and required connection hardware are ordered separately.
Capacity Selection
Choose the orifice according to the refrigerant, required evaporator capacity and actual operating conditions. The table below provides nominal capacity references for R134a, R404A/R507, R407C and R22.
These figures describe the installed valve with the selected orifice and a matching thermostatic element. Actual capacity at other operating temperatures requires application-specific selection.
Identification and Ordering
Orifice numbers such as 0X, 00 and 01 are size identifiers, rather than bore diameters in millimetres. Specify both the size and full Danfoss code when ordering.
Please provide the required quantity, existing valve identification, refrigerant and operating conditions when requesting a quotation from XIAXUE Refrigeration.
Technical Specifications
| Parameter | Specification |
|---|---|
| Brand | Danfoss |
| Product Type | Orifice Assembly with Filter |
| Compatible Valve Family | T2 / TE2 |
| Assembly Version | Flare Version |
| Orifice Sizes | 0X, 00, 01, 02, 03, 04, 05, 06 |
| Number of Variants | 8 |
| Filter Configuration | Filter for Flare Connection |
| Supplier-Listed Packing | 25 pieces/box |
| Sales Unit | Piece |
| Thermostatic Element / Valve Body | Ordered separately |
Model and Nominal Capacity Table
| Orifice | Danfoss Code | R134a kW | R404A/R507 kW | R407C kW | R22 kW |
|---|---|---|---|---|---|
| 0X | 068-2002 | 0.68 | 0.64 | 0.92 | 0.90 |
| 00 | 068-2003 | 1.20 | 1.30 | 1.80 | 1.80 |
| 01 | 068-2010 | 2.10 | 2.60 | 3.50 | 3.50 |
| 02 | 068-2015 | 2.60 | 3.70 | 4.80 | 4.70 |
| 03 | 068-2006 | 4.30 | 6.30 | 8.10 | 8.00 |
| 04 | 068-2007 | 6.40 | 9.90 | 12.40 | 12.10 |
| 05 | 068-2008 | 8.40 | 13.00 | 16.50 | 16.70 |
| 06 | 068-2009 | 10.10 | 15.50 | 19.70 | 19.70 |
Reference conditions: evaporating temperature 4.4°C, condensing temperature 38°C, and liquid temperature ahead of the valve 37°C. These are nominal installed-valve capacities.
| Orifice Size and Code |
No. 0X - 068-2002, No. 00 - 068-2003, No. 01 - 068-2010, No. 02 - 068-2015, No. 03 - 068-2006, No. 04 - 068-2007, No. 05 - 068-2008, No. 06 - 068-2009 |
|---|