Danfoss T2 / TE2 Orifice Assemblies with Filter for Solder Adaptor
Product Description
Danfoss T2 / TE2 Orifice Assemblies with Filter for Solder Adaptor provide the specified insert-and-filter configuration for compatible solder-adaptor installations. Eight sizes are available, from No. 0X, code 068-2089, through No. 06, code 068-2096.
These components are used with a separate solder adaptor and matching valve assembly. Select the required orifice size and adaptor connection when preparing an order.
Matching the Assembly
The solder-adaptor arrangement uses its own filter configuration. Match the full Danfoss code to the valve connection arrangement when selecting a replacement. The adaptor itself is supplied separately. Danfoss solder-adaptor orifice information
Capacity and Application
Select the assembly using the refrigerant, evaporator duty and operating temperatures. The nominal figures below apply to the installed valve with the selected orifice and a matching thermostatic element.
For enquiries, provide the exact code number, quantity, existing valve identification and adaptor size. For new selections, include the refrigerant, required capacity, evaporating temperature and condensing conditions.
Technical Specifications
| Parameter | Specification |
|---|---|
| Brand | Danfoss |
| Product Type | Orifice Assembly with Filter |
| Compatible Valve Family | T2 / TE2 |
| Assembly Version | For Solder Adaptor |
| Orifice Sizes | 0X, 00, 01, 02, 03, 04, 05, 06 |
| Number of Variants | 8 |
| Filter Configuration | Filter for Solder Adaptor |
| Supplier-Listed Packing | 25 pieces/carton |
| Sales Unit | Piece |
| Solder Adaptor | Ordered separately |
| Thermostatic Element / Valve Body | Ordered separately |
Model and Nominal Capacity Table
| Orifice | Danfoss Code | R134a kW | R404A/R507 kW | R407C kW | R22 kW |
|---|---|---|---|---|---|
| 0X | 068-2089 | 0.68 | 0.64 | 0.92 | 0.90 |
| 00 | 068-2090 | 1.20 | 1.30 | 1.80 | 1.80 |
| 01 | 068-2091 | 2.10 | 2.60 | 3.50 | 3.50 |
| 02 | 068-2092 | 2.60 | 3.70 | 4.80 | 4.70 |
| 03 | 068-2093 | 4.30 | 6.30 | 8.10 | 8.00 |
| 04 | 068-2094 | 6.40 | 9.90 | 12.40 | 12.10 |
| 05 | 068-2095 | 8.40 | 13.00 | 16.50 | 16.70 |
| 06 | 068-2096 | 10.10 | 15.50 | 19.70 | 19.70 |
Reference conditions: evaporating temperature 4.4°C, condensing temperature 38°C, and liquid temperature ahead of the valve 37°C. Actual capacity requires selection at the operating conditions.
| Orifice Size and Code |
No. 0X - 068-2089, No. 00 - 068-2090, No. 01 - 068-2091, No. 02 - 068-2092, No. 03 - 068-2093, No. 04 - 068-2094, No. 05 - 068-2095, No. 06 - 068-2096 |
|---|